Energy Meter Current Transformer


Energy Meter Current Transformer
Features
- 10(80)A/4mA, Rb=10Ω, turns ratio 1:2500
- Max current 80A, 0.1 class, DC immune error<3%
- Dual core winding double insulated, OD Φ32mm
- Mounting holes 2-Φ6.4mm, distance 22.5mm
- Used for single or three phase energy meters
Specifications
Part Number | DSB80-25A |
Description | Energy Meter Current Transformer |
Structure Of Winding | Toroidal |
Phase | Single |
Input / Output | 10(80)A/4mA |
Max. Current | 80 A |
Turns Ratio (typical) | 1:2500 |
Phase Shift Error | 5′ (20% Rated Current) |
Burden (Rb) | 10 Ω |
Accuracy Class | 0.1 Class |
DC Immune Error | <3% |
Core Inside | Nanocrystalline & Fe-based Amorphous Dual Core |
Encapsulation | Insulation Tape & Heat-shrink Sleeve |
Busbar Type | Built-in busbar |
Mounting Method | Through-holes for Screw Fixing |
Application | Meters, Instruments |
Accept Customized | Yes |